Field Office Compliance - Work Request


Work Request ID - 3111
Winterset City Of Stp - 310640694
2255 NORWOOD AVENUE Winterset, IA 50273
Madison County

FO 5

Describe Request
6/5/2015 Site Survey for Winterset Phase 1 Improvements TERRY KIRSCHENMAN
Request Files
File Name File Type File Date
Work Request Resolution
Report
File Name File Type File Date Note
Comments
6/8/2015 All inhabitable buildings are greater than 2,000 feet away. All identified wells are greater than 1,500 feet away. No public impoundments are located in the vacinity of the WWTP. The City owns ample property at the site to maintain at least 25 feet from the property line in all directions. The upgraded pumping station is adjacent to the existing pumping station and is surrounded by other treatment units. The proposed location of the new TF/SC basins and UV disinfection equipment is south of the TF units and north of the east EQ basin. This location does not reduce any of the existing separation distances and the existing distances significantly exceed the minimum distances required by 567 IAC 64.2(3). Based on the information provided by the engineer and in our files, the site appears to be acceptable. TOM ATKINSON
Compliance Tracking
Action Type Date Completed Date Comment Delete