Field Office Compliance - Spill


Magellan Pipeline Co, Llc - Des Moines - 311467744
2503 SE 43RD ST. Des Moines, IA 50327
Polk County

FO 5

Spill Number:
122315-RPM-2220
Spill Location:
41.562610, -93.526620
Spill County:
Polk
FO 5
Incident Report
Reported By:
  • Sec: 17
  • Tier: 78
  • Range: R2
  • Lat:
  • Long:
Responsible Party
Spill Contact
Select Name Program Type
MAGELLAN PIPELINE COMPANY, L.P. Minor Industrial Owner
MAGELLAN PIPELINE COMPANY, LP Minor Industrial Mailing Contact
Magellan Midstream Partners, L.P. Title V Public Contact
Lance Whisman Title V Public Contact
Material Information
Report
Document Name Type File Date Note
01-22-2016\122315-RPM-2220.pdf
Report
12/24/2015 30 day
01-22-2016\30 day report - 122315-RPM-2220.pdf
Report
12/24/2015 30-day written report
File Name File Type File Date Note
Comments
1/7/2016 On December 23, 2015 they put an extension off the end (opening) of the leak detection pipe and put a tub under the extension to collect water/product that was coming out of the leak detection pipe. They also used absorbents to clean up any liquid on the ground surface. They identified the affected area (area of soil affected by the spill) as extending approximately 40' out from the southeast side of the tank and at its furthest extent from the tank about 40' wide. Soil conditions were wet and the depth the material had gone into the ground varied from 2" to 1' deep. The water/gasoline mix was confined inside the dike around the tank. They called J Pettiecord Excavating to come the following morning to remove all affected soils around the tank and began pumping gasoline from tank 2701 to another nearby tank. Tank 2701 was just being put into service. It has a capacity of 350,000 barrels but only contained 50,000 barrels of gasoline when the spill was discovered. BILL GIBBONS
1/7/2016 On December 24, 2015 at 12:30 PM Ted Petersen and Bill Gibbons with IDNR Field Office 5 met Tristan Grover at the site. Tristan explained how the tank was constructed. The tank sides sit on a concrete ring wall while the floor has a layer of sand underneath it. The layer of sand has a clay liner below it. There are a series of perforated pipes in the sand under the floor that are used for leak detection. Each pipe is in an isolated section beneath the tank and employees monitor the outlet of the pipe(s) to see if there is any water or fuel coming out the end of the pipe which would indicate a leak. In this case one of the pipes that outlets on the southeast side of the tank had a slow stream coming out if it that was a mixture of water and gasoline. Tristan took us to Tank 2701 which is a new tank that was recently put into service. J Pettiecord Excavating was already on-site and was removing the soils affected by the release. There was a pipe extending out of the end of the leak detection pipe and a small stream of water/gasoline was going into the tub and according to Tristan the amount coming out of the pipe was much less than when the release was first discovered. We met Joshua Pellegrm the Operations Supervisor and he said they had problems with the pump at first but it had been fixed and they were now pumping the remaining gasoline out Tank 2701 into another nearby tank. He said they should be done pumping by the end of the weekend (Sunday, December 27th). The next step would be to bring in a crew that would remove the residual fuel from the tank and ready it for another group to enter and evaluate the tank (find the leak in the floor of the tank). That process would begin Monday, December 28, 2015. Joshua also told Ted and Bill that when they did the hydrotest on the tank (Fall 2015) to test it for leaks before putting it into service there was a small amount of water coming out of the same leak detection pipe during the test. They thought it might be the sand below the tank was wet and extended the test another 48 hours to see if there was a leak. The water quit coming out of the pipe and they believed it was just a matter of draining some excess water that was already in the sand and determined the tank was ready to put into use. BILL GIBBONS
1/7/2016 On Monday, December 28, 2015 Bill Gibbons received an update from Tristan Grover. Tristan reported they had completed pumping the gasoline out of the tank on Sunday, December 27, 2015. The material coming out of the leak detection pipe is now down to a slow drip. There is a crew coming from Kansas City that will prepare the tank for entry by the middle of the week (Week of December 28, 2015). BILL GIBBONS
1/7/2016 On Tuesday, January 5, 2015 Bill Gibbons received an update from Tristan Grover. Last week the tank was opened and prepared for entry (ventilated so that it was vapor free). They started cleaning the tank on Monday, January 4, 2016. The cleaning should be completed Thursday, January 7, 2016 and they will begin making a determination as to the cause and location of the leak. All soil samples collected after the affected soils were removed came back as non-detect. BILL GIBBONS
7/29/2016 On July 26, 2016 we received a summary report for the incident. The report summarized activities to-date and stated they would be attempting to flush-out the remaining gasoline in the interstitial space below the tank by introducing water into a cathodic protection tube that bisects the interstitial space and collecting the fluid coming out of two of the leak detection lines (pipes) with a vacuum tank. BILL GIBBONS
Public Water Suppliers
Name Supply Type PWS ID Operator: Name / Phone Number Contacted
Compliance Tracking
Action Type Date Completed Date Comment Delete