Field Office Compliance - Field Activity: Staff Action ID - 36180


Magellan Pipeline Co, Llc - Des Moines - 311467744
2503 SE 43RD ST. Des Moines, IA 50327
Polk County

FO 5

Activity Report
File Name File Type File Date Note
Comments
3/5/2010 I talked to Tristan Grover with Magellan on Friday, March 5, 2009 to get an update on the spill and sent the following E-mail to Adam Broughton in Emergency Response: Adam, I received a call from Tristan Grover with Magellan regarding the spill on Tuesday, March 2, 2010 near the truck loading rack at the Magellan Terminal in Pleasant Hill. He called to update me on progress. Since my visit to the site on Wednesday Morning they have continued to recover free product from the three recovery wells. Seneca is there with the vacuum truck from 7:00 AM to around 5:00 to 6:00 PM. They are giving the wells a chance to recharge overnight. They are looking at making changes to the pumps they have in the recovery wells to operate in a fashion where free product can be pumped out of the wells at a much higher rate thus eliminating the need for a vacuum truck every day. Late Wednesday Afternoon the finished saw cutting the concrete over the pipeline and are in the process of thawing the ground so they can excavate the soil around the pipeline. They don’t plan on doing an extensive over-excavation at this time due the number of pipelines under the ground in this area however the soil that is removed will be taken to Metro East. Tristan has contacted Becky Wherman about taking the contaminated soil to the landfill. They collected a soil sample next to recovery well No. 3 and took it to Keystone Lab for analysis (TEH). The results of this sample will be used to obtain permission to dispose of the excavated soil. They will probably dig out around the pipeline over the weekend. I will be going back to the site on Monday, March 8, 2010 at 1:00 PM to meet with Tristan and Steven Steward the Area Supervisor. Sincerely, Bill Gibbons Field Office 5 BILL GIBBONS
3/4/2010 On Wednesday March 3, 2010 I made a visit to the site and sent Adam the following E-mail: I went to the site and met with Tristan Grover, Steven Steward (Area Supervisor), Rodger Teasdale (Operations Supervisor), and David Hruby with Apex. The release was in the area of the truck loading rack and was from a pipeline that goes from a manifold (south) to the loading rack. They suspect the leak was in that pipeline near the loading rack. There are three recovery wells just east of the truck loading rack that are currently being used to recover free product from a spill two years ago. They checked the three recovery wells for free product. Recovery wells 1 and 2 had 6" of product (similar to amount before spill). Recovery well 3 had12" of free product and they determined it was partly fresh product in the well. Magellan reviewed inventory records and think the release started on or about February 17, 2010. Seneca has been on-site with a vacuum truck since yesterday at 4:00 PM and have recovered approximately 600 gallons from Recovery Well 3. Magellan is looking at putting in a different pumps in Recovery Wells 1 & 2 for more aggressive recovery. There is a perimeter of 8 monitoring wells around the truck rack area and 7 of the 8 wells were checked for free product. None of the wells had free product. They took groundwater samples from 6 of the wells (wells 1, 2, 3, 4, 5, & 8) to be analyzed for TEH. The pipeline was disconnected at both ends and pumped out. The plan is to excavate the pipe to see where the leak occurred. They will leave the excavation trench open and plan to recover product from the trench.. The pipeline was originally installed approximately 1940. Tristan Grover will call me when the pipe is excavated to look at the situation and determine how to proceed. Sincerely, Bill Gibbons BILL GIBBONS
3/4/2010 On Tuesday, March 2, 2010 Magellan reported a Spill to Adam Broughton with the Emergency Response Section. Adam sent out the following E-mail: Just got off the phone with Tristan. Based on calculations form inventory they are estimating the release at 916 barrels (41,220 gallons). The release is from a line that runs from a diesel storage tank to the load out rack. This is the same area as the previous release 2 years ago. They checked several of the monitoring wells and found what may be new product in one of the recovery wells. They plan to pump down the well and see what recovery they get. They are also sampling the six outlying wells for OA-1 and OA-2 to determine if there is any impact. They plan to update us tomorrow. Thanks, Adam Adam H. Broughton IV Environmental Specialist Senior Iowa Department of Natural Resources Emergency Response & Homeland Security Unit BILL GIBBONS
Compliance Tracking
Action Type Date Completed Date Comment Delete