Field Office Compliance - Field Activity - 43952


SAPP BROS TRAVEL CENTERS - 310335492
2496 210TH AVE Percival, IA 51648
Fremont County

FO 4

Activity Report
Document Name Type File Date Note
percival122111.sappbrostruckstop.pdf
Inspection Report (public)
12/21/2011 audit
File Name File Type File Date Note
Comments
1/17/2012 dispenser 5/6 leakl with no containment. stained backfill. dispenser3/4 leak at fuel filter with no containment. stained backfill. significant fuel leak dispenser 7/8 with no containment. wet fittings diesel #22 Damp fittings on many other dispensers. Free product discovered in diesel tank pit monitoring well (sw well) fuel in all spill basin at fill pipes. Tightness tests after flood reopening unavailable. Please fax test to out office/ Leaks must be repaired asap. RHONDA PAHL
Compliance Tracking
Action Type Date Completed Date Comment Delete