Comments
1/28/2014 From: McCurnin, Mike [mailto:[email protected]] Sent: Tuesday, January 28, 2014 10:34 AM To: Gastineau, Janet [DNR] Cc: Adams, Mike; Woodruff, Carter Subject: RE: SWTP MOR Janet: The turibidity spike occurred upon start-up (unit had been off for near three days) and was very short lived………below 0.3 ntu w/in 4 minutes and below 0.1 ntu w/in 5 minutes. From: Gastineau, Janet [DNR] [mailto:[email protected]] Sent: Tuesday, January 28, 2014 9:46 AM To: McCurnin, Mike Subject: SWTP MOR At the Saylorville plant there was a high reading of 0.970 NTU reported on membrane unit #1 on December 14, 2013. Please confirm/provide documentation of compliance based on the requirement that the individual filter effluent turbidity must not exceed 0.5 NTU in 2 consecutive measurements taken 15 minutes apart, at the end of the first four hours of continuous filter operation. JANET GASTINEAU
Compliance Tracking
Action Type Date Completed Date Comment Delete
"
"