1/31/2023 Nate called on January 9th, 2023, and reported that they had foaming at their plant again. He suspected Prestage may be the cause due to an increase in non-process flow. I visited the plant on January 18th, 2023, and discussed with Nate what was going on. He showed that Prestage had increased their non-process flow by approximately 200,000 gallons for a period of 3 days which coincided with the foaming be observed. I met with Tom Ford of Prestage, and he reported that they had an issue with their DAF around that time that would have caused an increase in their raw water bypass which goes to the non-process lift station. The raw water bypass is a portion DAF effluent, and not untreated wastewater. The rest of the DAF effluent goes to the anaerobic lagoons for further treatment. He reported that the visual appearance of the DAF effluent looked normal and didn't think that was the cause. Nate did not grab any samples from Prestage during the period of increased non-process flow so, it is unknown whether that effluent would have met the TA limits. The flow reported did meet the TA limits, so at this time there is no data to suggest Prestage violated their TA. I recommended to Nate to set up his auto sampler daily at Prestage's main lift station to see if the effluent quality changes over time. I told him he would not need to run samples everyday, but if he saw something out of the ordinary, he could. JACOB DONAGHY