Field Office Compliance - Assistance


Assistance ID - 88533
Des Moines Water Works - 310338211
9966 Maffitt Lake Dr Cumming, IA 50061
Dallas County

FO 5

Report
File Name File Type File Date Note
Comments
8/29/2016 8/29/16 I saw DMWW staff Friday for an inspection and they provided me with this attachment. For comparison, they had the following levels reported 8/10/16: Latest MICROCYSTIN Results: 1. Fleur Drive Finished Water: Mon – Thurs results = .938 ppb, 3.05 ppb, 0.19 ppb, and 0.109 ppb 2. Raccoon River: Mon – Thurs results = 50 ppb, 35 ppb, >5 ppb, and > 5 ppb (yet to dilute and test for WED/THURS) 3. Des Moines River: Mon – Thurs results = .105 ppb, .196 ppb, .151 ppb, and 0.463 ppb (more than tripled since Monday) 4. McMullen & SWTP Finished Water: Non-detects in finished 5. We currently have microcystin levels in each river that are above the action level of 0.3 ppb. I can confidently state that we have never (knowingly) been in this position. Cyanotoxin levels are reported to be under control and testing continues daily. They are still chlorinating backwash return and sending solids to the lagoon across the river. Janet JANET GASTINEAU
"
"