Field Office Compliance - Assistance


Assistance ID - 87561
Fort Dodge Water Supply - 310385018
600 PHINNEY PARK Dr Fort Dodge, IA 50501
Webster County

FO 2

Report
File Name File Type File Date Note
Comments
7/20/2016 Pender called about a positive Routine Total coliform bacteria sample at Murphy Gas, which is the same location that had a positive earlier in the year. No E. coli was present. We discussed checking the building and the area for signs of problems (cross-connections, etc.) According to the operator who took samples at the site, the faucet aerator may be damaged. They were not able to remove it prior to sampling. According to Pender, it does not appear that there is a chlorine residual problem in the area (result was about 1.7 ppm Total chlorine), but Pender will continue to evaluate the situation. We discussed the RTCR requirement to take Repeats at the original site and at nearby sites that are upstream and downstream. Pender will change one of the sites that was used last time, because he has identified a better (closer) sample location. I also clarified that Pender is allowed to make changes to the bacteria sampling plan when needed. If they make a good faith effort to identify a problem at the Murphy site and only find that the sample tap is no longer in adequate condition to be used as a bacteria sample tap, Pender may chose a new bacteria sample site. (But he must still take the required Repeat at Murphy now.) Per the GWR, Pender must take TG samples at each well that may have contributed water to the sample (presumably all wells). I clarified that Repeat samples must be taken within 24 hours of notification, unless there are extenuating circumstances. (not likely for Fort Dodge) SCOTT WILSON