Field Office Compliance - Assistance


Assistance ID - 82366
Washington City Of Stp - 310643746
1065 WEST BUCHANAN ST Washington, IA 52353
Washington County

FO 6

Report
File Name File Type File Date Note
Comments
11/10/2015 Conference call at 1500 on 11/10/2015 with Fred (and Brent Hinson and Jason), Rob Baker (Fox Engineering), Ron Lutovsky (Iowa Renewable Energy), and Lonnie Litchfield (IRE) concerning IRE's sample results for last month (10/27/15 smples) - they were over the limits in the treatment agreement. Just got analytical reports today: TSS: 1160 mg/L; BOD: 49,700 mg/L (COD: 22,000 mg/L, so something is wrong with the BOD analysis). That is 7500 lbs BOD, over the design capacity of the Washington WWTP. Will be getting 11/2 and 11/3 sample results from lab (Keystone) tomorrow (around 55,000 mg/ COD from internal sampling). Seem to get better mixing with higher flow through the floc tubes, based on internal sampling. Identified a new waste stream (methanol) that wasn't included in the pilot test - they think it heavily influenced the results. It isn't presently contributing to the treatment process. The IRE pretreatment system is not designed to treat BOD. IRE will not discharge any more to the POTW until they know they can meet limits - will truck it to the Des Moines POTW. POTW says IRE is doing a good job of keeping them informed. JIM KACER