Field Office Compliance - Assistance


Assistance ID - 79348
Des Moines Water Works - 310338211
9966 Maffitt Lake Dr Cumming, IA 50061
Dallas County

FO 5

Report
File Name File Type File Date Note
Comments
6/15/2015 From: McCurnin, Mike [mailto:[email protected]] Sent: Monday, June 15, 2015 12:07 PM To: Gastineau, Janet [DNR] Cc: Water Production Supervisors; Olmstead, Regina Subject: RE: SWTP MOR Janet: Attached please find revised components of the SWTP May-2015 MOR……….. I adjusted the max NTU to 0.71 ntu……and have recorded 1 measurement above 0.3 ntu for 5/15/2015. Also attached is a trend that shows the duration of this event to be less than 8 minutes in length and occurred within approximately 10 minutes of significant high service pump changes (2 pumps off and 2 pumps on). Thanks for bringing this to my attention. From: Gastineau, Janet [DNR] [mailto:[email protected]] Sent: Monday, June 15, 2015 8:24 AM To: McCurnin, Mike Subject: SWTP MOR CFE turbidity shows a high of 0.53 May 15th but # of readings >0.3 is reported as 0. Can you correct this one way or the other and resubmit this page? Thanks. JANET GASTINEAU
"
"