Field Office Compliance - Assistance


Assistance ID - 66529
Magellan Pipeline Co, Llc - Des Moines - 311467744
2503 SE 43RD ST. Des Moines, IA 50327
Polk County

FO 5

Report
File Name File Type File Date Note
Comments
1/29/2014 On January 24, 2014 Apex collected samples at the oil/water separator and at the West Coffer Dam. The analytical laboratory results from both samples (received on January 24, 2014) showed Total BTEX <9 ug/L. BILL GIBBONS
1/24/2014 I talked to Tristan Grover on January 24, 2014 to clarify the details of the incident on November 20, 2013. The material spilled on the collection pans and on the ground was completely cleaned up and none of the material reached the oil/water separator or piping going into the separator. This is why they did not clean and inspect the separator after the incident but pumped it out as a precaution. BILL GIBBONS
1/23/2014 On January 23, 2014 at 12:30 PM I received a call from Tristan Grover with Magellan. Tristan was calling to report an exceedence with their NPDES Permit for the Oil/Water separator for the train loading rack area. They exceeded the limit for BTEX (limit 100 ug/L) with total BTEX being 113.14 ug/L. They did not exceed the limit for benzene however Xylenes were 89.1 ug/L. Tristan said there was a spill of off-road diesel fuel at the train loading rack on November 20, 2014 when 2 gallons were spilled. Most of the diesel fuel went into the spill containment but approximately 1/2 gallon went onto the ground next to the collection pans. The spilled fuel was recovered from the drip pans and the and the ground and the recovered fuel was introduced into the oil/water separator system. The oil/water separator was pumped out however they did not do a cleaning of the separator. The sampling results for December 2013 came back below detection limits however the January sample exceeded the permitted limit for BTEX. Apex collected a sample at the coffer dam and Benzene, Toluene and Ethylbenzene came back non-detect however Xylenes were 8 ug/L. The sample from the oil/water separator was collected on January 13, 2014 and Tristan Grover was notified of the exceedence by Apex at 4:20 PM on January 22, 2014. Tristan said Apex is going to re-sample the oil/water separator on Friday, January 24, 2014 and will include the laboratory results on the 5-day written report. BILL GIBBONS