Field Office Compliance - Assistance


Assistance ID - 46169
Magellan Pipeline Co, Llc - Des Moines - 311467744
2503 SE 43RD ST. Des Moines, IA 50327
Polk County

FO 5

Report
File Name File Type File Date Note
Comments
4/10/2012 On April 2, 2012 We received a follow up report from Apex Companies on behalf of Magellan for Total BTEX exceeding permit requirements titled "March 2012 NPDES Permit Five-Day Response". The report concluded that a solvent used to clean the repaired area of the Oil/Water Separator was the cause of the high level of total BTEX. The report stated that the residual from the solvent used in the repair should not be a factor in the upcoming April monitoring event. BILL GIBBONS
3/30/2012 On Friday, March 30, 2012 I called Tristan Grover. I told him they needed to report the result on their Monthly Operation Report and to include an explanation. I asked Tristan if they could obtain a sample of the influent (water going into the separator). Tristan said there was not a good way to obtain an influent sample. Tristan asked if they were going to receive a Notice of Violation or fine because of the high result for March. I told Tristan at this point we knew they were working to solve the problem and those measures were not warranted at this time. I told Tristan if the problem continued we would likely send them a letter requiring them to correct the problem. Tristan is doing research on the fiberglass material used in the repair of the separator. BILL GIBBONS
3/30/2012 On Thursday, March 30, 2012 at 3:30 PM I received a call from Tristan Grover (515-971-1560). They had done the sampling for the oil/water separator at the Des Moines Terminal and exceeded the permitted level for this outfall for Total BTEX. Tristan said they were <5 ug/L for benzene however for Total BTEX Xylene was 247 and total BTEX was 319. Tristan said they had recently overhauled the separator by completely cleaning it and replacing the filters. He said while the unit was being cleaned (by Seneca) they discovered the wall between the clean water chamber and incoming water was cracked thus allowing influent to seep through into the clean water chamber. Seneca then hired a company to repair the crack, put the new filters into the separator and put it back into use. Two days later they took a sample for March 2012 and the laboratory results came back exceeding permitted levels for Total BTEX. Tristan said he believes the fiberglass repair may have influenced the sample from contact of the water with the repaired area (additional curing of the fiberglass repair). I asked Tristan to consult with the company that did the repairs and find out what type of resin they were using to see if it could have influenced/altered laboratory results (if Xylene was a component of the resin and curing process). In addition I asked if the repair was influencing results how long the curing process might take before a representative sample could be obtained and analyzed. Tristan said he would contact the company who did the repairs and call me back. Tristan was greatly concerned about reporting this result on their monthly operation report (MOR). I told Tristan they would have to report the results in their MOR but to provide a narrative in the report as to why they believed the exceedence had taken place. Tristan said they obtained the laboratory results at 10:00 AM (Thursday, March 29, 2012) and had reported to me at 3:30 PM (the same day). BILL GIBBONS