9/20/2011 Received a call from Kam Reeves at Ottumwa WWTP to discuss sample results. In late August there had been a water main break near MidAmerican in the vicinity of were the coal tar had been removed. Water from the main break was going to the storm sewer and had a sheen/odor to it. Since the storm sewer goes to the WWTP (combined sewers), plant staff diverted flow to the storm water pond rather than take it through the plant. A sample had been collected at the Elm St. pump station and that is the results we had. Kam had e-mailed a copy to me. Most of the parameters were non-detectable except for: (ug/l) benzene 55.9, chlorloform 5.7, toluene 437, xylene 1380, ethylbenzene 449, napthalene 719, O/G 471. The results are somewhat over the standard of 750 ppb for discharge to sanitary sewer. However, I told Kam it would probalby be OK to run the pond contents through the plant because the contaminants have been diluted by other storm water, and have been sitting in an open pond for 2 weeks with hot weather so there should have been volatilization occurring. PAUL BRANDT