Field Office Compliance - Assistance


Assistance ID - 34214
New Hampton City Of Stp - 310650074
800 SOUTH LOCUST AVENUE New Hampton, IA 50659
Chickasaw County

FO 1

Report
File Name File Type File Date Note
Comments
5/20/2011 Tim was concerned that a sludge sample result exceeded the nickel ceiling value. Sample was 441 mg/kg. Ceiling value is 420. tim reported that this was a grab sample from setteled sludge in the bottom of the tank. I suggested he have the lab re-run the test. If the lab verifies the sample, he should take more samples in different parts of the tank to average them. Sludge samples should be composite anyway. SUSAN MILLER