Comments
5/12/2026 On Tue, May 12, 2026 at 2:32?PM Loehr, Matt <[email protected]> wrote: Brian, Per our conversation this morning: The site was replacing a pump when they inadvertently left a valve open allowing an overapplication of aluminum sulfate to an SCU tank. Our plan moving forward, is to send increments of 100,000 gallons of water from the SCU tank to the low volume wastewater treatment pond. The gate will be closed to not allow a discharge to the outfall, and to allow the alum time to flocculate in the pond. A substantial change in pH would be representative of an issue with solidification, and with every 100,000 gallons of water we will take a grab pH sample to ensure the additional alum isn’t causing a pH imbalance in the pond. If the pH changes by a value of more than 1.5 we will pause our activity to determine the next best course of action moving forward. In presenting more information about the dilution of the alum. The pond at maximum capacity holds 50,000,000 gallons of water, and the total volume of the SCU tank is 657,622 gallons. If the pond is only holding 40,000,000 gallons of water, we’re discharging <1.7% of pond’s total volume from the SCU tank. If you have any questions of concerns feel free to contact me. Thank you, Matt Loehr | Sr. Environmental Specialist Alliant Energy Ottumwa Generation Station 20775 Power Plant Rd | Ottumwa, IA 52501 Office: (641) 935-2971 Cell: (641) 328-3283 BRIAN LEE
5/12/2026 Excess aluminum sulfate added to the treatment system due to malfunction. Dilution thought to take care of the issue, but I told Matt to ensure there is no water quality issue with effluent. May be able to test for aluminum sulfate let alone indicate no issues with TSS and pH testing. I asked for a summary of the event via email. BRIAN LEE