Field Office Compliance - Assistance


Assistance ID - 136694
West Liberty City Of Stp - 310648869
615 EAST A STREET West Liberty, IA 52776
Muscatine County

FO 6

Report
File Name File Type File Date Note
Comments
1/14/2026 Juergens indicated he had a Phosphorus sample come back on 12/29 of 19 mg/l. He believes that was a mistake, suggesting that all samples from 2024 and 2025 the highest result in 2024 was 4.46mg/l and an highest monthly average was 2.08 mg/L. In 2025 the highest daily max was 4.97mg/l and the 12 month highest average was 2.15mg/l. He asked how to report this since "obviously the test couldn't have been accurate". He added that the second highest reading for the month of December was .61 with the rest of the weekly samples coming back non-detect. I asked Craig if an outside lab does their phosphorus analysis? If so, he should ask them to look at their QA/QC protocols to see if they can identify a possible analytical or reporting error. If they can, they can provide a corrected copy of the analysis and we can use that in lieu of the erroneous data in the body of the DMR. If lab error can not be identified, then technically, he has to be report and use the result he has in the DMR monthly calculation but he could add a comment in the comment box stating the result is suspect because all samples collected prior to and after the result were normal. He should comment on what the monthly average would have been w/o the suspect result. TERRY JONES