9/17/2024 Glenn Carlson called FO4 about a group of 4 houses that were built in the mid 1900s and have a shared lateral. I advised Glenn that, per Section 11.1.d or the Iowa WW Design Standards, a pipe carrying wastewater from 4 residences located on separate property units (separate parcels) is not a "sanitary sewer service connection." It is an extension of the sanitary sewer collection system subject to DNR construction permitting requirements and design requirements. Glenn asked about exceptions. I advised Glenn that DNR is not actively seeking existing shared laterals and, where they currently exist, they could be allowed to continue as long as they are working. If they have issues that can be addressed by maintenance, such as annual jetting or a discreet point repair, they can probably be allowed to continue. If, however, they need to replace the shared line, they will need to go through the construction permitting process or put in separate laterals for each property unit. DAN OLSON