Field Office Compliance - Assistance


Assistance ID - 127610
Bayer Cropscience Lp - 6909 - 310203151
2500 Wiggens Rd Muscatine, IA 52761
Muscatine County

FO 6

Report
File Name File Type File Date Note
Comments
4/7/2023 3/22/2023 1252: Email assist to Elana Becker of Bayer Crop Science regarding booster pumps in the distribution system. She had requested the code citation that related to the requirement. The email read as follows (including her original email): Elana, Here is the citation from 10 States Standards on that. The private booster pumps must be equipped with automatic shutoffs or pressure controllers to maintain at least 20 psi in the suction line under all operating conditions. [Recommended Standards for Water Works 6.4.c]. This would relate to the information that you provided that there are booster pumps in tall units (A-Unit, potable shack). Thank you, Jon On Wed, Mar 22, 2023 at 12:48?PM Elana Becker <elana.becker@bayer.com> wrote: Hi Jon, Would you be able to direct me to or send me the regulations that support the requirement for the booster pumps requiring 20 psi be maintained under all conditions and the regulation for requiring independent/auxiliary power sources to the wells? Thank you in advance! Elana Becker Environmental Engineer JON RYK
"
"