Report
File Name File Type File Date Note
Comments
8/4/2022 The City of Davenport, WPC Wastewater Treatment NPDES #8222003 requested a bypass of secondary effluent outfall #001, around the UV disinfection system as part of the UV Disinfection construction project. The City reported that high flow events have resulted in a higher-than-anticipated hydraulic grade line through the final clarifiers. A hydraulic review by the city indicated there is a baffle wall located in a below-ground structure that should be removed to reduce the head loss through this structure. The baffle wall was constructed as part of the original plant construction in the 1970s. The baffle wall is no longer needed and engineers suggested it be removed. Because flow can only be shut off to the plant for a maximum of about 4 hours at one time, several shutdowns will be required on separate days. The volume of secondary effluent bypassed around UV disinfection for each shut down will be approximately 30,000 gallons. The contractor anticipates approximately 10 shutdowns to complete the work, though it may take fewer or more shutdowns than this. The city plan was discussed with Erik Wiklund and Ben Hucka in Des Moines with no objection. TERRY JONES