Field Office Compliance - Assistance


Assistance ID - 123773
Harlan City Of Stp - 310640749
910 MAPLE ROAD Harlan, IA 51537
Shelby County

FO 4

Report
File Name File Type File Date Note
Comments
4/29/2022 Harlan WW Operator Tim Gessert called my state cell at 10:52 on 4/20/2022 to report that Harlan wouldn’t meet their geometric mean limit for E. coli in April. He reported that their first 4 samples ran 167, 248, 106, and 209 MPN. Their UV bulbs have 8000 hours on them and Tim thought that they should still be good. They cleaned the bulbs after the second sample. When that did not result in improvement by the fourth sample, Tim personally observed the cleaning of the bulbs and made sure that they were cleaned thoroughly. Their fifth sample was 52.9 MPN. We discussed the fact that, while the geomean limit in the permit is based on a minimum of 5 samples, it is permissible to collect more than 5 samples in a calendar month. Tim stated that he would collect 2 more samples in April. Tim called my state cell phone at 10:37 on 4/29/2022 and left a message stating that, “I think we got our E. coli figured out now.” I returned his call at 13:28 on the same date. He reported that he had determined that their high E. coli results had been due to incomplete cleaning of the UV tubes and valve being 100% open instead of partially open to slow flow and allow for more contact in the UV chamber. He also reported that their last 2 samples were in the 50’s. DAN OLSON