Field Office Compliance - Assistance


Assistance ID - 112288
Des Moines Water Works - 310338211
9966 Maffitt Lake Dr Cumming, IA 50061
Dallas County

FO 5

Report
File Name File Type File Date Note
Comments
4/9/2020 Gastineau, Janet <[email protected]> Mon, Apr 6, 9:18 AM (3 days ago) to Mike, Kyle FOr determining compliance with the requirement to keep the percent of readings less than or equal to 0.3 NTU you only need to count the 15 minute CFE readings, not what happens between them. So if the highest of the 15 minute readings was not this value, please revise the MOR and resubmit. Thanks! On Sun, Apr 5, 2020 at 4:28 PM Adams, Mike <[email protected]> wrote: The finished turbidity spiked to 0.36 NTU’s for 1 minute on 2/16/2020. The brief spike was not one of the 96 readings. Should we use one of the 96 readings for the daily highest? Mike Adams | Water Production Supervisor of Operations Des Moines Water Works | WATER YOU CAN TRUST FOR LIFE 2201 George Flagg Parkway | Des Moines, Iowa 50321 | www.dmww.com Phone: (515) 283-8710 | fax: (515) 283-8757 | e-mail: [email protected] From: Gastineau, Janet <[email protected]> Sent: Friday, April 03, 2020 1:32 PM To: Danley, Kyle <[email protected]>; Adams, Mike <[email protected]> Subject: February McMullen MOR There was a 0.36 NTU recorded as the highest daily reading 2/16/2020, but it's not listed under the previous column for the number of readings greater than 0.3 NTU. According to this, there should be at least one 15 minute reading included. Please make the correction to the turbidity data page 1 of 2 and submit it no later than 4/10/2020. Thanks. -- JANET GASTINEAU
"
"