W/Wisard
 Water/Wastewater Information System and Records Database
Database Instructions Document
Database Instructions Video



Facility Info
PWSID Facility:
Owner Address: ATTN NATHAN CASEY, 2201 GEORGE FLAGG PKWY, DES MOINES, IA 50321
PWSID Number: IA7727031 Owner Contact: DES MOINES WATER WORKS
Owner Phone: 515-283-8709 Facility Type: Community
County: POLK Field Office: FO5
Population Served: 246055 Status: Active

Project Details
Project #: W2025-0171
DWSRF Number:
Project Description: 2024 NE Booster Station Project
DNR Project Manager: Matt Phoenix, PE
email: [email protected]
Phone: (515) 725-0298
Consultant:
Submitted Without Engineer: No

Construction Permit/Approvals
Categories Received Reviewed Finalized Final Action Permit Number Download
Pump Station 1/21/2025 3/25/2025 6/9/2025 Permitted 2025-0350W Download
Description : an above grade booster station including two (2) horizontal, centrifugal, double suction split case pumps with capacities of 1,400 gpm at 250’ TDH; chemical feed equipment for sodium hypochlorite and ammonium sulfate; a diesel powered generator; and 437 feet of 12-inch diameter AWWA C900 D...
Variance 5/9/2025 5/13/2025 6/2/2025 Approved Download
Description : Waiver from requirement to use day tanks for chemical feeds in the booster station. Chemicals will instead be fed directly from bulk storage and monitored 24/7 by DMWW personnel.

SRF
This project has no SRF information.

Contracts
This project has no Contracts information.

Environmental Reviews
No Data Available for Environment Review